Redundant Package Air Conditioner
Redundant Packaged Air conditioner is twin system inbuilt in single cabinet and can be mounted from outside of Telecom Shelter for cooling of Infra inside the shelter. This AC is mostly suitable for shelter sites where internal space is challenge and require 24×7 cooling. The twin system works alternately as per the heat load inside and acts as backup to other circuit in case of any component failure. Both the system working are logically managed by smart logic controller and the system combined offer reliable cooling for critical telecom cooling.
Capacity
Product | Type | Capacity |
230VAC Twin Packaged AC | Wall Mount | 2×1.25 TR, 2×1.5TR & 2×2 TR |
48VDC Twin Packaged AC | Wall Mount | 2×1 TR & 2×1.25TR |
Specifications
DESCRIPTION | UNITS | IK-PAC-44A-2 | IK-PAC-70A-2 | IK-PAC-70A-2-3PH |
UNIT | ||||
NOMINAL COOLING CAPACITY | TR(btu/hr) | 2X1.25TR(15000) | 2 x 2TR(24000) | 2X2TR(24000) |
NO.OF REFERIGERANT CIRCUITS | No’s | 2 | 2 | 2 |
AIR FLOW/CIRCUIT | cu.m/hr. | 1275 | 2023 | 2023 |
AIR FLOW/CIRCUIT | CFM | 750 | 1190 | 1190 |
Input Power/ each circuit | W | 1570 | 2350 | 2350 |
Input current/ each circuit | Amps | 7 | 10 | 4 |
ELECTRICAL POWER SUPPLY : | ||||
(A) POWER SUPPLY | 230 V- 1PH-50HZ | 230 V- 1PH-50HZ | 415V – 3PH – 50HZ | |
(B) CIRCUIT CURRENT CAPACITY | A | 15 | 20 | 20 |
(C) DISCONNECT FUSE SWITCH | A | 32 | 32 | 32 |
OVERALL DIMENSIONS | ||||
(A) WIDTH | mm | 665 | 665 | 665 |
(B) DEPTH | mm | 743 | 743 | 743 |
(C) HEIGHT | mm | 938 | 938 | 938 |
Panels thickness | ||||
IDU | ||||
OUTER SIDE PANELS | mm | 0.9 | 0.9 | 0.9 |
INNER SIDE PANELS | mm | 1.2 | 1.2 | 1.2 |
DRIP TRAY, BLANK OFF PLATES & SERVICE PANELS | mm | 0.9 | 0.9 | 0.9 |
MOTOR MTG PANEL | mm | 1.2 | 1.2 | 1.2 |
ODU | ||||
BASE | mm | 1.2 | 1.2 | 1.2 |
CORNERS | mm | 1.2 | 1.2 | 1.2 |
TOP, SIDE PANELS | mm | 0.9 | 0.9 | 0.9 |
REAR PANEL | mm | 1.2 | 1.2 | 1.2 |
Features
- Inbuilt Redundancy for critical applications
- High Sensible Cooling
- High CFM for faster removal of heat
- No use of plastic components to ensure fire protection
- GI powder coated body
- High Static backward curve fan
- Microprocessor controller
- Inbuilt Safety for high/low temperature & Voltage
- Over/Underload Protection
- High/Low pressure Switch